4 MAG816 - Installation and Operation Manual
1. GENERAL INFORMATION
The MAG816 is a conventional microprocessor fire control panel, designed according
to EN54 Standard requirements. The panel provides for monitoring and reporting
fire events in up to 16 separate zones, depending on the installed configuration.
The MAG816 must be installed according to the Fire Alarm Installation Regulations,
mandatory for the territory of the respective country. The electrical power supply to
the panel must be isolated and must not be capable of being accidentally switched
off. The power switch-off board should display a clear FIRE ALARM - DO NOT
SWITCH OFF label.
2. TECHNICAL SPECIFICATIONS
2.1 General Technical Specications of MAG816
▪ Maximum number of detectors per zone: - Up to 32 conventional detectors with
consumption < 200µА at a normal mode;
- Unlimited number of manual call points.
▪ Thresholds for zone conditions:
• 0 ÷ 2 mA - Open circuit fault condition.
• 2 ÷ 10 mA - Normal condition.
• 10 ÷110 mA - Fire alarm condition.
• > 110 mA - Short circuit condition.
▪ Power Supply:
• Main Power Supply ~ 230V AC ±10%
2А Fuse, T -Type.
• Stand-by Power Supply 1 Accumulator battery 12V/ 18Ah
Dimensions - 167х181х76mm
Voltage Output - U
CHARGE
= 13,8V
Current Output - I
MAX
= 2A
7А Fuse, Resettable (PTC)
Battery connection: with a at terminal
lug Ø5mm
▪ Consumption from 230V in normal
working mode and a fully charged
battery:
• At 4 zones (1 Zone Expander) 2,1VA
• At 16 zones (4 Zone Expanders) 4,2VA
▪ Consumption from the battery at mains
power supply failure in normal working
mode:
• With connected 1 Zone Expander 130mA
• With connected 4 Zone Expanders 260mA
▪ Consumption from the battery in Fire alarm
condition:
• At 1 Zone Expander, Fire in 1 zone 330mA
• At 1 Zone Expander, Fire in 4 zones 720mA
▪ Outputs:
• Sounder circuits SND1÷SND4 +24V/ 0.3A
(control module) Resettable (PTC) Fuse