15
ESP Addressable and Conventional Fire Protection • www.espuk.com
MAG816 - 8 Zone Fire Panel expandable to 16 zones
■ Up to 16 programmable zones
■ Up to 16 sounder circuits
■ Active end of line monitoring and head removal
■ Up to 32 fire detectors per zone
■ Unlimited number of call points per zone
■ Integral evacuate alarm button
■ Repeater facility
■ ‘Class change’ facility
■ Enable/disable security key
■ One man walk test facility
■ Volt free fire/fault change over relay
■ Individual sounder circuit fault ID
■ Indiv
idual zo
ne/sounder isolate
■ Alarm delay options
■ Certified to EN54–2/4
■ Requires 1 x 12V batteries
■ ABS casing
Made in
EN54
FIRE ZONE / SOUNDER OUTPUT MATRIX
Number of zone cards fitted 2 3 4 2 3 1 2 1
Number of sounder cards fitted 0 0 0 1 1 2 2 3
Number of zones 8 12 16 8 12 4 8 4
Number of sounder outputs 4 4 4 8 8 12 12 16
NB The MAG816 features 4 sounder circuits. Space is provided for up to 4 extra
expansion cards of any combination. Sounder cards carry 4 sounder circuits,
Zone cards carry 4 fire zones. The MAG816 is supplied as standard with 8 fire zones
and 4 sounder circuits.
MAGZC816
4 Zone Expander Card
MAGSC816
4 Zone Sounder Expander Card
OUTPUTS On board sounder circuits (4) 300mA @ 24V fuse resettable (PTC)
Sounder expander cards (4) 150mA @ 24V fuse resettable (PTC)
Fault/fire relay Volt free 500mA @ 24V (max load)
Auxiliary output 24VDC (300mA fused)
ENVIRONMENT Working Temperature 0 to 40ºC
Storage Temperature -20 to 60ºC
Humidity 0 to 93%
Dimensions (mm) 456 x 350 x 125mm
Weight 4.2 KG
INPUTS Max. detectors per zone 32
Thresholds for 0 - 2 mA (Fault condition)
zone conditions 2 - 10 mA (Normal condition)
10 - 110 mA (Fire condition)
110mA - + Short (Fault condition)
POWER Mains fail consumption 130mA (1 zone expander)
260mA (4 zone expanders)
Mains supply 230 VAC ± 10%
Standby supply 1 x 18ah 12V S.L.A. Batteries
Power availability 0.7 amps
MAGPro Fireline Catalogue.qxp_Layout 1 16/06/2014 15:35 Page 15